Product Description
Gas Train For Pressure Reducing System
We offer Gas Train for Pressure Reducing System, which comprises filters, slam-shut off valve, pressure regulator, safety relief valve and flame arrestor. The system helps to remove dust/ dirt particles from gas that can damage the regulator parts.
Working:
- Slam shut off valve remains open
- Outlet pressure of the regulator exceeds the permissible limits, the slam shut off valve senses it through the impulse line
- instant shut-off of supply to the downstream system
- Equipped with safety relief valve
- Preset to higher pressure than the slam shut off valve pressure for working when slam shut off valve fails to operate
- The outlet of the safety relief valve is vented well above the roof